Title: INFORMATIVE VALUE OF ELECTRICAL CABLE REACTION TO FIRE CLASS

INFORMATIVE VALUE OF ELECTRICAL CABLE REACTION TO FIRE CLASS
J. Martinka;T. Stefko;I. Wachter
1314-2704
English
19
6.3
Electrical cables are one of the key components of green building technologies. They are crucial for the operating of many green building technologies (e.g. power transfer from the solar cell to other building electric devices). For fire safety level assessment of electrical cables installed in green buildings are used their fire characteristics. The reaction to fire is the fundamental and most important fire characteristic of electrical cables. Nevertheless, it is used almost exclusively in the prescriptive approach to fire safety of structures (in the prescriptive approach, the law or technical regulation specifies the minimum class of reaction to fire of electrical cables in certain areas, e.g. escape routes). However, the actual contribution of an electrical cable to the development of a fire and a decrease in visibility in a fire compartment is not obvious from the reaction to fire class. In this paper considered fire scenario is selected: the amount of released heat and the loss in visibility in the fire compartment caused by the fire of electric cables (15 mm in diameter) classified as fire B1ca, B2ca and Cca reaction to fire classes and additional classifications for smoke s1 and s2. Space used in the considered fire scenario have 20 x 10 x 8 m, in which 5 (unprotected) electric cables were installed side by side under the ceiling. Six cases were analysed under same conditions of fire scenario (class B1ca - s1, B1ca - s2, B2ca - s1, B2ca - s2, Cca - s1, Cca - s2). In each case analysed, all 5 electrical cables had the same class of reaction to fire and the cables were ignited by Joule heat. Three values of the total amount of released heat and smoke extinction area were investigated for each case. The first was value (released heat and smoke) investigated was the most favourable (minimum), the second least favourable (maximum), and the third mean value, which still allow the cable to be classified into the appropriate fire reaction class (or additional classification). The data obtained show that there are also significant differences between the cables with the same fire reaction class (or additional classification) in terms of heat released and loss of visibility in the fire compartment, during fire.
conference
19th International Multidisciplinary Scientific GeoConference SGEM 2019
19th International Multidisciplinary Scientific GeoConference SGEM 2019, 9 - 11 December, 2019
Proceedings Paper
STEF92 Technology
International Multidisciplinary Scientific GeoConference-SGEM
Bulgarian Acad Sci; Acad Sci Czech Republ; Latvian Acad Sci; Polish Acad Sci; Russian Acad Sci; Serbian Acad Sci & Arts; Slovak Acad Sci; Natl Acad Sci Ukraine; Natl Acad Sci Armenia; Sci Council Japan; World Acad Sci; European Acad Sci, Arts & Letters; Ac
309-316
9 - 11 December, 2019
website
cdrom
6695
electrical cable; reaction to fire class; fire scenario; heat release rate; visibility in fire compartment.

25th SGEM International Conference on Earth & Planetary Sciences


International GeoConference SGEM2025
27 June - 6 July, 2025 / Albena, Bulgaria

Read More
   

SGEM Vienna GREEN "Green Science for Green Life"


Extended Scientific Sessions SGEM Vienna GREEN
3 -6 December, 2025 / Vienna, Austria

Read More
   

A scientific platform for Art-Inspired Scientists!


The Magical World Where Science meets Art
Vienna, Austria

Read More